Panier Mon compte

Contacteurs SCHNEIDER > Bloc contacts auxiliaires & Disj. moteur SCHNEIDER

GV2ME06

Disjoncteur moteur SCHNEIDER - 1-1.6A - 3 Pôles - déclencheur magnéto-thermique | SCHNEIDER

Livraison ou retrait magasin
En stock ( + 30 pcs)

Informations produit

Caractéristiques techniques principales :

rangeTeSys
TeSys Deca
product nameTeSys GV2
TeSys Deca
product or component typeCircuit breaker
device short nameGV2ME
device applicationMotor
trip unit technologyThermal-magnetic


Informations complémentaires :

poles description3P
network typeAC
utilisation categoryAC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
network frequency50/60 Hz conforming to IEC 60947-4-1
fixing mode35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
operating positionAny position
motor power kW0.37 kW at 400/415 V AC 50/60 Hz
0.37 kW at 500 V AC 50/60 Hz
0.75 kW at 690 V AC 50/60 Hz
0.55 kW at 400/415 V AC 50/60 Hz
0.55 kW at 500 V AC 50/60 Hz
0.75 kW at 500 V AC 50/60 Hz
1.1 kW at 690 V AC 50/60 Hz
breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
control typePush-button
[In] rated current1.6 A
thermal protection adjustment range1…1.6 A
magnetic tripping current22.5 A
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current1.6 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
power dissipation per pole2.5 W
mechanical durability100000 cycles
electrical durability100000 cycles for AC-3 at 440 V
maximum operating rate25 cyc/h
rated dutyContinuous conforming to IEC 60947-4-1
tightening torque1.7 N.m on screw clamp terminals
suitability for isolationYes conforming to IEC 60947-1
phase failure sensitivityYes conforming to IEC 60947-4-1
height89 mm
width45 mm
depth78.5 mm
net weight0.26 kg
colourDark grey

PLAN DU SITE


Logo DRIM France png

BESOIN D'AIDE ? 04 72 14 09 08 - info@drim.fr